Pintek Products High Voltage Probe HVP-40M ( 40KVDC, 600MΩ , Analog Meter ) Features :DC 40KV CAT II Pollution 2600MΩ Impedance25KV ± 2%, 40KV ± 3%T.C. 200 ppm/oCPositive Polarity only.Resolution 1KVNeed not power.CE、IEC1010 SPECIFICATIONS ( 20 ± 5℃, RH < 80% ) ! WARNING !?Before taking any measurements, first connect the alligator clip of this probe to earth ground and make sure connection is electrically good.Input impedance:600MΩMaximum operation voltage:40KV DC , CAT II , Pollution 2Polarity:Positive onlyDisplay:Analog indicateAccuracy:Factory calibrater 25KV ± 2%?????????FULL scale 40KV ± 3 %Temperature Coefficient:≦ 200ppm / ℃Maximum loading Current:≦ 70μA Maximum loading power:≦ 3 wattVoltage Range:40KV / 1 RangeVoltage resolution:1KVPower source:Need not powerOperating temperature:0 ℃ ~ + 50 ℃Storage temperature:- 20 ℃ ~ + 70 ℃Ground lead length:90cm ( 35 " )Dimensions:420 L x 80ψWeight :360g Manual Dimension Comparison High Voltage Probe Selection Guide Please write down your comment on this product, and click Add to Inquiry List for inquiry Add to Inquiry List Review Inquiry List Back